Micropilot FMR51, FMR52 FOUNDATION Fieldbus Operating menu
Endress+Hauser 127
Tube diameter
Navigation  Setup → Tube diameter
Prerequisite Tank type (→  126) = Bypass / pipe
Description Specify diameter of bypass or stilling well.
User entry 0 to 9.999 m
Factory setting 0 m
Medium group
Navigation  Setup → Medium group
Prerequisite Medium type (→  138) = Liquid
Description Select medium group.
Selection Others
Water based (DC >= 4)
Factory setting Others
Additional information This parameter roughly specifies the dielectric constant (DC) of the medium. For a more
detailed definition of the DC use the Medium property parameter (→  138).
The Medium group parameter presets the Medium property parameter (→  138) as
follows:
Medium group Medium property (→  138)
Others Unknown
Water based (DC >= 4) DC 4 ... 7
The Medium property parameter can be changed at a later point of time. However,
when doing so, the Medium group parameter retains its value. Only the Medium
property parameter is relevant for the signal evaluation.
The measuring range may be reduced for small dielectric constants. For details refer
to the Technical Information (TI) of the respective device.
Empty calibration
Navigation  Setup → Empty calibr.
Description Specify the distance E between the process connection and the minimum level (0%). This
defines the starting point of the measuring range.