Operating menu Micropilot FMR51, FMR52 FOUNDATION Fieldbus
128 Endress+Hauser
User entry Depending on the antenna
Factory setting Depending on the antenna
Additional information
A0019486
27 Empty calibration (E) for level measurements in liquids
The measuring range starts at the point at which the radar beam hits the tank or silo
bottom. In the case of dished boiler ends or conical outlets levels below this point can
not be measured.
Full calibration
Navigation Setup → Full calibr.
Description Specify the distance F between the minimum level (0%) and the maximum level (100%).
User entry Depending on the antenna
Factory setting Depending on the antenna
Additional information
A0019487
28 Full calibration (F) for level measurements in liquids