Operating menu Micropilot FMR51, FMR52 FOUNDATION Fieldbus
130 Endress+Hauser
Signal quality
Navigation  Setup → Signal quality
Description Displays the signal quality of the level echo.
Additional information Meaning of the display options
Strong
The evaluated echo exceeds the threshold by at least 10 dB.
Medium
The evaluated echo exceeds the threshold by at least 5 dB.
Weak
The evaluated echo exceeds the threshold by less than 5 dB.
No signal
The device does not find a usable echo.
The signal quality indicated in this parameter always refers to the currently evaluated
echo: either the level echo or the tank bottome echo. To differentiate between these two,
the quality of the tank bottom echo echo is always displayed in brackets.
In case of a lost echo (Signal quality = No signal) the device generates the following
error message:
F941, for Output echo lost (→  153) = Alarm.
S941, if another option has been selected in Output echo lost (→  153).
Confirm distance
Navigation Setup → Confirm distance
Description Specify, whether the measured distance matches the real distance.
Depending on the selection the device automatically sets the range of mapping.
Selection Manual map
Distance ok
Distance unknown
Distance too small
*
Distance too big
*
Tank empty
Factory map
Factory setting Distance unknown
Additional information Meaning of the options
Manual map
To be selected if the range of mapping is to be defined manually in the Mapping end
point parameter (→  131). In this case it is not necessary to confirm the distance.
Distance ok
To be selected if the measured distance matches the actual distance. The device
performs a mapping.
Distance unknown
To be selected if the actual distance is unknown. A mapping can not be performed in this
case.
* Visibility depends on order options or device settings