Max. filling speed liquid
Navigation  Setup → Advanced setup → Level → Max. fill liquid
Prerequisite Medium type (→  138) = Liquid
Description Select expected maximum filling speed.
Selection Slow < 1cm (0,4in) /min
Medium < 10cm (4in) /min
Standard < 1m (40in) /min
Fast < 2m (80in) /min
Very fast > 2m (80in) /min
No filter / test
Factory setting Depending on the Tank type parameter (→  126)
Additional information Max. filling speed liquid is preset by Tank type (→  126). It can, however, be adjusted
to the process in the vessel at any time. If Tank type (→  126) is changed again at a
later point of time, it may be necessary to repeat the fine adjustment.
Max. draining speed liquid
Navigation  Setup → Advanced setup → Level → Max drain liquid
Prerequisite Medium type (→  138) = Liquid
Description Select expected maximum draining speed.
Selection Slow < 1cm (0,4in) /min
Medium < 10cm (4in) /min
Standard < 1m (40in) /min
Fast < 2m (80in) /min
Very fast > 2m (80in) /min
No filter / test
Factory setting Depending on the Tank type parameter (→  126)
Additional information Max. draining speed liquid (→  139) is preset by Tank type (→  126). It can,
however, be adjusted to the process in the vessel at any time. If Tank type (→  126) is
changed again at a later point of time, it may be necessary to repeat the fine adjustment.
Advanced process conditions
Navigation  Setup → Advanced setup → Level → Adv. conditions
Description Specify additional process conditions (if required).