Commissioning (block-based operation) Micropilot FMR51, FMR52 FOUNDATION Fieldbus
84 Endress+Hauser
12.5 Configuration of a level measurement
The Setup method can also be used to configure the measurement. It is called up via
the SETUP (TRDSUP) Transducer Block.
A0016933
R = Reference point of the measurement E = Empty calibration (= Zero point)
D = Distance F = Full calibration (= span)
L = Level
Step Block Parameter Action
1 SETUP (TRDSUP) Distance unit
(distance_unit)
Select distance unit.
Selection:
• 1010: m
• 1013: mm
• 1018: ft
• 1019: in
2 SETUP (TRDSUP) Tank type (tank_type) Select tank type.
Selection:
• 1271: Process vessel with agitator
• 1272: Process vessel standard
• 1273: Storage vessel
• 1274: Wave guide antenna
• 1279: Sphere
• 32816: Bypass / pipe
• 33013: Open channel
• 33094: Stilling well
3 SETUP (TRDSUP) Tube diameter
(tube_diameter)
1)
Enter the diameter of the bypass or stilling well.
4 SETUP (TRDSUP) Medium group
(medium_group)
Select medium group.
Selection:
• 316: water based (DC>4)
• 256: other (DC≥ 1.9)
5 SETUP (TRDSUP) Empty calibration
(empty_calibration)
Enter the distance E between the reference point
R and the minimum level (0%).
6 SETUP (TRDSUP) Full calibration
(full_calibration)
Enter distance F between the minimum (0%) and
maximum (100%) level.
7 SETUP (TRDSUP) Level (level) Displays the measured level L.