Commissioning (block-based operation) Micropilot FMR51, FMR52 FOUNDATION Fieldbus
84 Endress+Hauser
12.5 Configuration of a level measurement
The Setup method can also be used to configure the measurement. It is called up via
the SETUP (TRDSUP) Transducer Block.
F
L
D
E
100%
0%
R
A0016933
R = Reference point of the measurement E = Empty calibration (= Zero point)
D = Distance F = Full calibration (= span)
L = Level
Step Block Parameter Action
1 SETUP (TRDSUP) Distance unit
(distance_unit)
Select distance unit.
Selection:
1010: m
1013: mm
1018: ft
1019: in
2 SETUP (TRDSUP) Tank type (tank_type) Select tank type.
Selection:
1271: Process vessel with agitator
1272: Process vessel standard
1273: Storage vessel
1274: Wave guide antenna
1279: Sphere
32816: Bypass / pipe
33013: Open channel
33094: Stilling well
3 SETUP (TRDSUP) Tube diameter
(tube_diameter)
1)
Enter the diameter of the bypass or stilling well.
4 SETUP (TRDSUP) Medium group
(medium_group)
Select medium group.
Selection:
316: water based (DC>4)
256: other (DC≥ 1.9)
5 SETUP (TRDSUP) Empty calibration
(empty_calibration)
Enter the distance E between the reference point
R and the minimum level (0%).
6 SETUP (TRDSUP) Full calibration
(full_calibration)
Enter distance F between the minimum (0%) and
maximum (100%) level.
7 SETUP (TRDSUP) Level (level) Displays the measured level L.