Micropilot FMR60
12 V. 4, Rev. 2, 19-03-2018 Endress+Hauser
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output (for HART devices)
Failsafe mode selectable (in accordance with NAMUR Recommendation NE 43):
Minimum alarm: 3.6 mA
Maximum alarm (= factory setting): 22 mA
Failsafe mode with user-selectable value: 3.59 to 22.5 mA
Local display
Status signal (in accordance with NAMUR Recommendation NE 107)
Plain text display
Operating tool via HART communication or service interface (CDI)
Status signal (in accordance with NAMUR Recommendation NE 107)
Plain text display
Linearization
The linearization function of the device allows the conversion of the measured value into any unit of
length or volume. Linearization tables for calculating the volume in cylindrical tanks are pre-
programmed. Other linearization tables of up to 32 value pairs can be entered manually or semi-
automatically.
Galvanic isolation
All circuits for the outputs are galvanically isolated from each other.
Protocol-specific data HART
Manufacturer ID 17 (0x11)
Device type ID 0x112B
HART specification 7.0
Device description files (DTM, DD) Information and files under:
www.endress.com
www.fieldcommgroup.org
HART load min. 250 Ω
HART device variables The measured values can be freely assigned to the device variables.
Measured values for PV (primary variable)
Level linearized
Distance
Electronic temperature
Relative echo amplitude
Area of incoupling
Analog output adv. diagnostics 1
Analog output adv. diagnostics 2
Measured values for SV, TV, FV (second, third and fourth variable)
Level linearized
Distance
Electronic temperature
Terminal voltage
Relative echo amplitude
Absolute echo amplitude
Area of incoupling
Analog output adv. diagnostics 1
Analog output adv. diagnostics 2
Supported functions Burst mode
Additional transmitter status
Wireless HART data
Minimum start-up voltage 16 V
Start-up current 3.6 mA
Start-up time 65 s
Minimum operating voltage 14.0 V