Micropilot FMR60
20 V. 4, Rev. 2, 19-03-2018 Endress+Hauser
"Power
supply,
output"
1)
"Approval"
2)
Terminal
voltage U at
device
Maximum load R,
depending on the supply voltage
U
0
of the power supply unit
C:
2-wire;
4-20mA
HART,
4-20mA
All 16 to 30 V
3)
R [ ]W
U
0
[V]
10
16
27
20 30 35
0
500
A0031746
1) Feature 020 in the product structure
2) Feature 010 in the product structure
3) If the Bluetooth modem is used, the minimum supply voltage increases by 2 V.
Integrated polarity reversal protection Yes
Permitted residual ripple with f = 0 to 100 Hz U
SS
< 1 V
Permitted residual ripple with f = 100 to 10 000 Hz U
SS
< 10 mV
Power consumption
"Power supply; Output"
1)
Power consumption
A: 2-wire; 4-20mA HART < 0.9 W
B: 2-wire; 4-20mA HART, switch output < 0.9 W
C: 2-wire; 4-20mA HART, 4-20mA < 2 x 0.7 W
1) Feature 020 of the product structure
Current consumption
HART
Nominal current 3.6 to 22 mA the start-up current for multidrop mode can be parametrized
(is set to 3.6 mA on delivery)
Breakdown signal (NAMUR NE43) adjustable: 3.59 to 22.5 mA
Power supply failure
Configuration is retained in the HistoROM (EEPROM).
Error messages (incl. value of operated hours counter) are stored.
Potential equalization
No special measures for potential equalization are required.
If the device is designed for hazardous areas, observe the information in the documentation
"Safety Instructions" (XA).