Micropilot FMR60
Endress+Hauser V. 4, Rev. 2, 19-03-2018 29
Inner nozzle diameterD Maximum nozzle height H
max
1)
100 to 150 mm (4 to 6 in) 1 450 mm (58 in)
≥ 150 mm (6 in) 2 200 mm (88 in)
1) In case of longer nozzles, a reduction of the measuring performance is to be expected.
Note the following if the antenna does not project out of the nozzle:
The end of the nozzle must be smooth and free from burrs. The edge of the nozzle should be
rounded if possible.
Mapping must be performed.
Please contact Endress+Hauser for applications with nozzles that are higher than indicated in
the table.
Information concerning threaded connections
When screwing in, turn by the hex bolt only.
Tool: open-ended wrench 55 mm
Maximum permissible torque: 50 Nm (36 lbf ft)
Container with heat
insulation
1
2
A0032207
If process temperatures are high, the device should be included in the usual container insulation
system (2) to prevent the electronics from heating as a result of thermal radiation or convection. The
insulation should not be higher than the neck of the device (1).