Micropilot FMR67B PROFINET with Ethernet-APL Commissioning
Endress+Hauser 49
9.5 Configuring the device
9.5.1 Level measurement in bulk solids
100%
F
A
R
L
D
E
0%
A0016934
 20 Configuration parameters for level measurement in bulk solids
R Reference point of measurement
A Length of antenna + 10 mm (0.4 in)
D Distance
L Level
E "Empty calibration" parameter (= 0 %)
F "Full calibration" parameter (= 100 %)
9.5.2 Commissioning with the Commissioning wizard
In FieldCare, DeviceCare, SmartBlue and on the display, the Commissioning wizard is
available to guide the user through the initial commissioning steps.
Complete this wizard to commission the device.
For each parameter, enter the appropriate value or select the appropriate option.
NOTE
If you exit the wizard before completing all required parameters, the changes you have
made will be saved. For this reason, the device may then be in an undefined state!
In this case, a reset to the default settings is recommended.
9.6 Recording the Echo curve
Record the current Echo curve as a reference echo curve for subsequent diagnostic
purposes
After the measurement has been configured, it is recommended to record the current Echo
curve as a reference echo curve.
The Save reference curve parameter in the Echo curve submenu is used to record the
Echo curve.