27 Switching behavior and signaling
Δs, e. g. Pump control at one tank
• 1 sensor (H level) connected at input channel 2 (terminals 33 and 34)
• 1 sensor (L level) connected at input channel 3 (terminals 37 and 38) .
Relay outputs of output channels 2 and 3 switch simultaneously→ 27, 29
This ensures, for example, that a pump can be switched on at L level and switched off at
H level.
Fault signaling for channel 1 must be switched off.
When using the Liquiphant FTL51B sensor with electronic insert FEL67, sensor (H level)
FEL67 must be set to MAX safety and sensor (L level) FEL67 must be set to MIN safety.