2.5 Rackbus RS-485 option
Wiring the bus Up to 25 Prolevel FMC 661 transmitters can be connected to the Rackbus RS-485.
Instructions for wiring and grounding the bus are to be found in Operating Instructions
BA 134F which is delivered with Prolevel instruments having the Rackbus RS-485 option.
The Prolevel can be wired as indicated in the inset in Fig. 2.9.
Note!
Terminal 61 is connected internally to the PE ground terminal strip
The screening must be grounded and have electrical continuity throughout — read
BA 134F for grounding instructions
Bus address and
termination
Fig. 2.10 shows the configuration elements
for remote operation of the Prolevel
FMC 661. Every transmitter must have a
unique bus address:
Switch off power, loosen screws and
open the terminal compartment
Set the address at DIP-switch SW1
(Example: 2 + 8 = 10)
For the last transmitter on the bus, i.e.
furthest away from the computer:
Switch in the terminal resistance at
DIP-switch SW2: OFF; ON; ON; OFF
Close front panel, tighten screws.
A
L1
L2 (> L1)
Master
Rpull
Rt
Master
Rpull
Rt
1
OFF
ON
60 61 62
2
E
OFF
ON
OFF
ON
60 61 6260
61
62
1
OFF
ON
60
61
62
2
E
OFF
ON
OFF
ON
60
61
62
60
61
62
B
PE
PE
Rt
150
Rt
150
PE
PE
BA142_19/20
Fig. 2.9:
Rackbus RS-485 topologies
showing setting of bus
termination resistance
Inset:
Suggestion for wiring the bus
SW1
12481632
150 392392
+5V
(=10)
ON
OFF
ON
OFF
RS-485
[EExia]IIC
B DGND A
L+ L-
L1 N
1b1a 2a 2b
- +
- +
SW2
BA142_21
bus termination
switch
address switch
terminal compartment
Fig. 2.10:
DIP-switches for bus address and termination
61
PE
60 62
Data B
Data A
Screen
Note!
Chapter 2: Installation Prolevel FMC 661
18 Endress+Hauser

Related product manuals