Short Instructions
..
Quick configuration for level measurement
Function Matrix Action
1 Reset transmitter V9H5
Enter 671
Press »E« to register entry
- Omit if commissioned as in Section 4.1
2 »Empty« calibration* V0H1
Fill vessel 040% full (probe covered)
Enter level in %, m, ft, etc.
Press »E« to register entry
3 »Full« calibration* V0H2
Fill vessel 60100% full
Enter level in %, m, ft, etc.
Press »E« to register entry
4 0/4 mA signal V0H3
V0H5
V0H6
Enter 0 for 020 mA signal, 1 for 420 mA signal
Press »E« to register entry
Enter level for 0/4 mA signal (if not 0)
Press »E« to register entry
Enter level for 20 mA signal (if not 100)
Press »E« to register entry
5 Relays 1a and 1b V1H0
V1H1
Enter level for switching in calibration units
Press »E« to register entry
Enter fail-safe mode: 0 = minimum, 1 = maximum
Press »E« to register
6 Relays 2a and 2b V1H5
V1H6
V1H9
Enter level for switching in calibration units
Press »E« to register entry
Enter fail-safe mode: 0 = minimum, 1 = maximum
Press »E« to register
Enter 1 = Relay 2 assigned to channel 1
Press »E« to register entry
* Can be performed in reverse order
+
+
4 yellow relay LEDs,
1 red alarm LED,
1 green operation LED LC display
Operation
Selects vertical matrix position
Selects horizontal matrix position
Select position V0H0
Selects next digit
Move decimal point
Increases value of digit
Decreases value of digit
Registers entry
Short Instructions Prolevel FMC 661