EasyManua.ls Logo

Endress+Hauser prolevel FMC 661 - Page 35

Endress+Hauser prolevel FMC 661
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Value for 4 mA and
20 mA
The 4mA (V0H5) and 20 mA (V0H6) values,
default values 0% and 100%, determine
the levels at which the analogue signal
range begins and ends.
Example:
4 mA = 20%,
20 mA = 80%
# Matrix Entry Remarks
1 V0H5 20 4mA value, 20 %
2 - »E« Register entry
3 V0H6 80 20 mA value, 80%
4 - »E« Register entry
Note!
Set in calibration/linearisation units
When V0H3 = 0, V0H5 = 0 mA value
Output on alarmThe analogue output can be set such that
it takes on distinctive values when a fault
with alarm is detected. Depending on the
setting in V1H3/V1H8, the relays may also
follow the analogue output. The entry is
made in V0H7:
0 = -10% of signal range
1 = +110% of signal range (default)
2 = last value is held
Example:
Output -10 % on alarm
# Matrix Entry Remarks
1 V0H7 0 -10% on alarm
2 - »E« Register entry
The current values set on an alarm are
shown in the table
V0H3 =
Current on alarm when V0H7 =
0: (-10%) 1: (+110%) 2: hold
0: 0
20 mA
-2 mA
22.0 mA last value
1: 4
20 mA
-2 mA
22.0 mA last value
Caution!
If setting 2 is chosen, the fault recognition system on the 0/420 mA signal line is
effectively deactivated. Although the transmitter recognises a fault, i.e. the alarm
relay de-energises and the associated LED lights, the signal output to any follow-up
instrumentation appears to indicate a correct measured value.
0%
100%
V0H5
V0H6
level
0/4 mA 20 mA
BA142_38
Fig. 4.12:
Value for 4 mA and 20 mA, V0H5 and V0H6
t
-2
4
0
22
20
V0H7
1 = +110%
2 = hold value
mA
BA142_39
0 = -10%
alarm
Fig. 4.13:
Output on alarm, V0H7
Note!
Caution!
Prolevel FMC 661 Chapter 4: Level Measurement
Endress+Hauser 31

Related product manuals