Linearisation for tanks
with conical outlet
You require a linearisation table, H/V or
H/G, max. 30 pairs in increasing order
Level H in %, m or ft
Volume V or weight G in customer units.
# Matrix Entry Remarks
1 V9H5 670 Reset
2 - »E« Register entry
3 V3H5 fo Zero frequency
4 - »E« Register entry
5V3H6
f Sensitivity
6 - »E« Register entry
7 V3H0 1 Volume units
8 - »E« Register entry
9 V2H1 0 Manual
10 - »E« Register entry
11 V2H2 1 Table no.
12 - »E« Register entry
13 V2H3 V/G
1
30
Volume/weight*
14 - »E« Register entry
15 V2H4 H
1
30
Level m or ft*
16 - »E« Register entry
17 V2H5 »E« Next table no.*
— springs to V2H3
*Repeat #13
17 until all values entered
18 V2H0 3 Activate "manual"
19 - »E« Register entry
20 V0H1 E Tank empty, current
volume in hl, gal
21 - »E« Register entry
22 V0H2 F Tank full, current
volume in hl, gal
23 - »E« Register entry
Note!
First pair ~ 0 % level, in %, m, ft.
last pair ~ 100 % level, in %, m, ft.
On error E602 or E604, correct table.
Re-activate linearisation in V2H0.
After linearisation
Volume/weight is displayed at V0H0
Level is displayed at V0H9
Next step
Set analogue output and relays in volume
or weight units, p. 3033.
Note!
1
2
3
4
5
6
7
8
H
V/G
V0H1
V0H2
V2H0...V2H5
BA142_51
»Empty« volume
E
(0
40%)
»Full« volume
F
(60
100%)
probe or sensor
covered
V2H4
H
1
H
2
H
30
V2H3
V/G
1
V/G
2
V/G
30
zero point of calibration =
zero point of linearisation
zero point of calibration
Fig. 7.2:
Parameters for calibration and linearisation in a tank
with conical outlet
Prolevel FMC 661 Chapter 7: Appendix
Endress+Hauser 47