If possible, install the sensor well clear of fittings such as valves, T-pieces, elbows, etc.
Compliance with the following inlet and outlet runs is necessary in order to ensure
measuring accuracy.
• Inlet run: ≥ 5 x DN
• Outlet run: ≥ 2 x DN
Fig. 11: Inlet and outlet run
3.2.4 Vibrations
Secure the piping and the sensor if vibration is severe.
"
Caution!
It is advisable to install sensor and transmitter separately if vibration is excessively
severe. Information on resistance to vibration and shockcan be found on → Page 80.
Fig. 12: Measures to prevent vibration of the measuring device