3.2.7 Nominal diameter and flow rate
The diameter of the pipe and the flow rate determine the nominal diameter of the sensor.
The optimum flow velocity is between 2...3 m/s. The velocity of flow (v), moreover, has
to be matched to the physical properties of the fluid:
• v < 2 m/s: for abrasive fluids such as potter's clay, lime milk, ore slurry, etc.
• v > 2 m/s: for fluids producing build-up such as wastewater sludge, etc.
!
Note!
Flow velocity can be increased, if necessary, by reducing the nominal diameter of the
sensor (see Section 3.2.6).
Promag W
Flow rate characteristic values - Promag W (SI units)
Nominal
diameter
Recommended
flow rate
Factory settings
[mm] [inch]
Min./max. full scale value
(v ~ 0.3 or 10 m/s)
Full scale value
Current output
(v ~ 2.5 m/s)
Pulse value
(~ 2 pulse/s)
Low flow cut off
(v ~ 0.04 m/s)
25 1" 9...300 dm
3
/min 75 dm
3
/min 0.50 dm
3
1dm
3
/min
32 1 1/4" 15...500 dm
3
/min 125 dm
3
/min 1.00 dm
3
2dm
3
/min
40 1 1/2" 25...700 dm
3
/min 200 dm
3
/min 1.50 dm
3
3dm
3
/min
50 2" 35...1100 dm
3
/min 300 dm
3
/min 2.50 dm
3
5dm
3
/min
65 2 1/2" 60...2000 dm
3
/min 500 dm
3
/min 5.00 dm
3
8dm
3
/min
80 3" 90...3000 dm
3
/min 750 dm
3
/min 5.00 dm
3
12 dm
3
/min
100 4" 145...4700 dm
3
/min 1200 dm
3
/min 10.00 dm
3
20 dm
3
/min
125 5" 220...7500 dm
3
/min 1850 dm
3
/min 15.00 dm
3
30 dm
3
/min
150 6" 20...600 m
3
/h 150 m
3
/h 0.025 m
3
2.5 m
3
/h
200 8" 35...1100 m
3
/h 300 m
3
/h 0.05 m
3
5.0 m
3
/h
250 10" 55...1700 m
3
/h 500 m
3
/h 0.05 m
3
7.5 m
3
/h
300 12" 80...2400 m
3
/h 750 m
3
/h 0.10 m
3
10 m
3
/h
350 14" 110...3300 m
3
/h 1000 m
3
/h 0.10 m
3
15 m
3
/h
400 16" 140...4200 m
3
/h 1200 m
3
/h 0.15 m
3
20 m
3
/h
450 18" 180...5400 m
3
/h 1500 m
3
/h 0.25 m
3
25 m
3
/h
500 20" 220...6600 m
3
/h 2000 m
3
/h 0.25 m
3
30 m
3
/h
600 24" 310...9600 m
3
/h 2500 m
3
/h 0.30 m
3
40 m
3
/h