5 Operation PROline Promag 10
54 Endress+Hauser
5.4.4 Universal / common practice HART commands
The following table contains all the universal and common practice commands
supported by Promag 10.
Command No.
HART command / Access type
Command data
(numeric data in decimal form)
Response data
(numeric data in decimal form)
Universal Commands
0 Read unique device identifier
Access type = Read
none The device identifier provides information on
the device and manufacturer; it cannot be
altered.
The response consists of a 12-byte device ID:
Byte 0: fixed value 254
Byte 1: manufacturer ID, 17 = E+H
Byte 2: device type ID, 69 = Promag 10
Byte 3: number of preambles
Byte 4: universal commands rev. no.
Byte 5: rev. no. device-specific commands
Byte 6: software revision
Byte 7: hardware revision
Byte 8: additional device information
Byte 9-11: device identification
1 Read primary process
variable
Access type = Read
none Byte 0: HART unit ID of the primary process
variable
Bytes 1-4: primary process variable
Factory setting:
Primary process variable = Volume flow
! Note!
Manufacturer-specific units are represented
using the HART unit ID “240".
2 Read the primary process
variable as current in mA and
percentage of the set
measuring range
Access type = Read
none Byte 0-3: current current of the primary
process variable in mA
Bytes 4-7: percentage of the set measuring
range
Factory setting:
Primary process variable = Volume flow