PROline Promag 10 5Operation
Endress+Hauser 59
5.4.5 Device status / error messages
You can read the extended device status, in this case, current error messages, via
command "48". The command delivers bit-encoded information (see table below).
!
Note!
Detailed information on the device status messages and error messages, and how
they are rectified, can be found on Page 67 ff.!
Bits not listed are not assigned.
Byte Bit Error no. Short error description (Page 67 ff. )
0
0 001 Serious device error.
1 011 Faulty amplifier EEPROM.
2 012 Error when accessing data of the amplifier EEPROM.
3 3 111 Totalizer checksum error
5 0 321 Coil current of sensor is outside tolerance.
7 3 351 Current output: the current flow is outside the set range.
8 3 359 Pulse output: the pulse output frequency is outside the set range.
10 7 401 Measuring tube partially filled or empty
11
2 461 EPD adjustment is not possible as the fluid conductivity is too low
or too high.
4 463 The EPD adjustment values for empty pipe or full pipe are
identical, i.e. faulty.
12 7 501 Loading new measuring amplifier software version. No other
commands possible at this point.
14 3 601 Positive zero return active.
18
3 691 Simulation of failsafe mode (outputs) active
4 692 Simulation volume flow