Commissioning Proline Promag 50
48 Endress+Hauser
5.5 Software settings
5.5.1 Device address
Has to be set for measuring devices with the following communication methods:
PROFIBUS DP/PA device address range 0 to 126, factory setting 126
The device address can be configured via:
Miniature switches see Hardware settings ä 41
Local operation see description below
!
Note!
The COMMISSIONING SETUP must be executed before setting the device address.
Calling the Communication Quick Setup
1.
F
Enter the function matrix (starting with measured value display)
2.
P
Select the group QUICK SETUP
F
Confirm selection
3.
N
Select the QUICK SETUP COMMUNICATION function
4. Intermediate step if configuration is blocked:
P
Enter the code 50
(confirm with
F
) and thus enable the configuration
5.
P
Go to Communication Quick Setup
6.
P
Select YES;
F
confirm selection
7.
F
Start Communication Quick Setup
8. Configure the individual functions/settings:
Via
P
-key, select option or enter number
Via
F
-key, confirm entry and go to next function
Via
Q
-key, return to Setup Commissioning function
(settings already made are retained)
All the available functions of the measuring device and their configuration options as well as
additional Quick Setups, if available, are described in detail in the "Description of Device
Functions" Operating Instructions. The related Operating Instructions can be found on the
CD-ROM.
The measuring device is ready for operation on completion of the Quick Setup.
5.6 Troubleshooting
A complete description of all the error messages is provided in the Operating Instructions on the
CD-ROM.
!
Note!
The output signals (e.g. pulse, frequency) of the measuring device must correspond to the
higher-order controller.