PROline Promag 53 3 Installation
Endress+Hauser 25
3.2.8 Length of c onnecting cable
In order to ensure measuring accuracy, comply with the following instructions when
installing the remote version:
Secure the cable run or route the cable in a conduit. Movement of the cable can falsify
the measuring signal, particularly if the fluid conductivity is low.
Route the cable well clear of electrical machines and switching elements.
Ensure potential equalization between sensor and transmitter, if necessary.
The permissible cable length Lmax depends on the fluid conductivity (Fig. 14).
A minimum conductivity of 20 µS/cm is required for measuring demineralized water.
Fig. 14: Permissible cable length for the remote version
Gray shaded area = permissible range
Lmax = length of connecting cable in [ft/m]
Medium conductivity in [
µS/cm]
Flow rate characteristic values - Promag H (US units)
Nominal diameter Recommended
flow rate
Factory settings
[inch] [mm]
min./max. full scale value
(v ~ 1.0 or 33 ft/s)
(v ~ 0.3 or 10 m/s)
Full scale value
(v ~ 8 ft/s)
(v ~ 2.5 m/s)
Pulse value
(~ 2 Pulse/s)
Low flow cutoff
(v ~ 0.1 ft/s)
(v ~ 0.04 m/s)
1/12" 2 0.015 to 0.5 gpm 0.1 gpm 0.001 gal 0.002 gpm
5/32" 4 0.07 to 2 gpm 0.5 gpm 0.005 gal 0.008 gpm
5/16" 8 0.25 to 8 gpm 2 gpm 0.02 gal 0.025 gpm
1/2" 15 1.0 to 27 gpm 6 gpm 0.05 gal 0.10 gpm
1" 25 2.5 to 80 gpm 18 gpm 0.20 gal 0.25 gpm
1-1/2" 40 7 to 190 gpm 50 gpm 0.50 gal 0.75 gpm
2" 50 10 to 300 gpm 75 gpm 0.50 gal 1.25 gpm
2-1/2" 65 16 to 500 gpm 130 gpm 1 gal 2.0 gpm
3" 80 24 to 800 gpm 200 gpm 2 gal 2.5 gpm
4" 100 40 to 1250 gpm 300 gpm 2 gal 4.0 gpm
F06-xxxxxxxx-05-xx-xx-xx-006