PROline Promag 53 4 Wiring
Endress+Hauser 51
4.1.2
Cable specifications
Coil cable
• 2 x 18 AWG (0.75 mm
2
) PVC cable with common, braided copper shield (Ø approx.
0.28"/7 mm)
• Conductor resistance: ≤ 0.011 Ω/ft (≤ 37 Ω/km)
• Capacitance: core/core, shield grounded: ≤ 36 pF/ft (≤ 120 pF/m)
• Permanent operating temperature: -4 to +176 °F (–20 to +80 °C)
• Cable cross-section: max. 16 AWG (2.5 mm
2
)
Signal cable:
• 3 x 20 AWG (0.38 mm
2
) PVC cable with common, braided copper shield (Ø approx.
0.28"/7 mm) and individually shielded cores
• With Empty Pipe Detection (EPD): 4 x 20 AWG (0.38 mm
2
) PVC cable with common,
braided copper shield (Ø approx. 0.28"/7 mm) and individually shielded cores
• Conductor resistance: ≤ 0.015 Ω/ft (≤ 50 Ω/km)
• Capacitance: core/shield: ≤ 128 pF/ft (≤ 420 pF/m)
• Permanent operating temperature: 4 to 176 °F (–20 to +80 °C)
• Cable cross-section: max. 16 AWG (2.5 mm
2
)
Fig. 30: Cable cross-section (a = Signal cable, b = Coil current cable)
1 = Core, 2 = Core insulation, 3 = Core shield, 4 = Core jacket, 5 = Core reinforcement, 6 = Cable shield,
7 = Outer jacket
As an option, E+H can also deliver reinforced connecting cables with an additional,
reinforcing metal braid. We recommend such cables for the following cases:
• Directly buried cable
• Danger of rodent attack
• Device used with NEMA 6P (IP 68) ingress protection
Operation in areas of severe electrical interference:
The measuring device complies with the general safety requirements in accordance
with EN 61010, the EMC requirements of EN 61326/A1, and NAMUR recommendation
NE 21.
"
Caution:
Grounding is by means of the ground terminals provided for the purpose inside the con-
nection housing. Keep the stripped and twisted lengths of cable shield to the terminals
as short as possible.
1
2
3
4
5
6
7
ab
F06-5xWxxxxx-04-11-08-xx-003