6 Commissioning PROline Promag 53
90 Endress+Hauser
“Batching” Quick Setup menu
HOME position → F → MEASURED VARIABLE (A)
MEASURED VARIABLE
→ O → QUICK SETUP (B)
QUICK SETUP
→ N → QUICK SETUP BATCHING / DOSING (1005)
Function No.
Function name Setting to select ( OS )
(Go to next function: press F )
1005 QUICK SETUP BATCHING / DOSING YES
After F is pressed by way of confirma-
tion, the Quick Setup menu calls up all
the subsequent functions in succession.
▼
! Warning:
Some of the functions listed below (with a gray background) are configured automatically, i.e. by the
measuring system.
6400 ASSIGN LOW FLOW CUTOFF VOLUME FLOW
6402 ON-VALUE LOW FLOW CUTOFF Recommended setting: See remarks on
Page 87, Function No. 6402.
6403 OFF-VALUE LOW FLOW CUTOFF 50%
6603 FLOW DAMPING 7
6404 PRESSURE SHOCK SUPPRESSION 0 seconds
7200 BATCH SELECTOR BATCH #1
7201 BATCH NAME BATCH #1
7202 ASSIGN BATCH VARIABLE VOLUME FLOW
7203 BATCH QUANTITY 0 [unit]
7204 FIX COMPENSATION QUANTITY 0 [unit]
7205 COMPENSATION MODE OFF
7208 BATCH STAGES 1
7209 INPUT FORMAT Value input
4700 ASSIGN RELAY BATCH VALVE 1
4780 TERMINAL NUMBER Output (display only)
7220 OPEN VALVE 1 0% or 0 [unit]
7240 MAXIMUM BATCH TIME 0 seconds (= switched off)
7241 MINIMUM BATCH TIME 0 seconds (= switched off)
7242 MAXIMUM BATCH QUANTITY 0 seconds (= switched off)
2200 ASSIGN (main line) BATCH NAME
2220 ASSIGN (multiplex main line) OFF
2400 ASSIGN (addition line) BATCH DOWNWARDS
2420 ASSIGN (multiplex addition line) OFF
2600 ASSIGN (information line) BATCHING KEYS
2620 ASSIGN (multiplex information line) OFF
▼
Back to the HOME position
→ Press and hold down Esc key (X) for longer than three seconds.
→ Repeatedly press and release Esc key (X) → exit the function matrix step by step