Proline Promag 53 FOUNDATION Fieldbus
Endress+Hauser 11
<
Remote version Promag 53***-******G/N*****
Connection between W/P/H sensor and Promag 53 FOUNDATION Fieldbus transmitter
Fig. 4: ➂ = Electrode circuit cable
➃ = Coil circuit cable
Connection between W/P/H sensor and Promag 53 FOUNDATION Fieldbus
transmitter
The grounding terminals are for connecting a potential-equalizing cable.
Cable specifications
The sensor cable connection between sensor and transmitter has an EEx i type of pro-
tection rating. The coil exciter circuit has an EEx e type of protection rating.
When the cable supplied by E+H is used, the maximum cable length at which the intrin-
sic safety of the circuit is ensured is 90 m (for IIC) or 200 m (for IIB).
"
Caution!
Use only the cable sets supplied by E+H.
Terminals 4 5 6 7 8 36 37 41 42
Pipe
GND
E1 S1 E2 S2 EPD
Designation Electrode circuit ➂ Coil circuit ➃
Functional
values
U = 60 V
P = 2.5 W
Intrinsically
safe circuit
[EEx ia] IIC/IIB no
U
o
= 37 V
I
o
= 25 mA
P
o
= 138 mW
L
o
IIC 50 mH
C
o
IIC 39 nF
L
o
IIB 200 mH
C
o
IIB 353 nF
F-53xxxxZZ-11-00-08-xx-000
.