Proline Promag 53 FOUNDATION Fieldbus
16 Endress+Hauser
<
0
Proof of intrinsic safety
Proof of intrinsic safety for the intrinsically safe bus segment can be made by using one
of the following models:
Entity model
FISCO model
Both models differ from one another by their consideration of the cable. While the FISCO
model considers the transmission line as distributed inductance and capacitance, the
basis of this consideration for the Entity model is concentrated inductance and capac-
itance. The result of this is that lower quantities of power can be transmitted with the
Entity model into the Ex area, and that the number of field devices instrument that can
be operated on a power repeater is therefore lower than with the FISCO model.
In the case of failure, instruments from different manufacturers can be exchanged when
their safety-relevant data is taken into consideration. This data is: electrical parameters,
device group and category, and the temperature class.
Both these models are briefly described in the following.
The Entity model
The Entity model is based on the observation that the cable represents concentrated
inductance and capacitance. The result is that less electrical power can be transmitted
into the area subject to the risk of explosion when compared with the FISCO model.
The following conditions must be met in the safety according to the entity model consid-
erations:
In addition, the following measures must be taken:
determine permissible explosion group for the bus segment
determine all effective energy stores (L
i
, C
i
, capacitance and inductance per unit
length)
check locally supplied operating units for galvanic isolation
harmonize temperature class and ambient temperature
!
Note:
Configuration example see Page 19
Field device
Hazardous area
Mandatory Power supply
Safe area
Maximum voltage
[U
i
]
Idle voltage of the
safety element [U
o
]
Maximum current
[I
i
]
Short-circuit current
[I
o
]
Maximum power
[P
i
]
[P
o
]
Effective internal capacitance
[C
i
]
+ cable capacitance
Maximum permitted external
capacitance [C
o
]
Effective internal inductance
[L
i
]
+ cable inductance
Maximum permitted external
inductance [L
o
]
Tab. 4: General dependencies