EasyManua.ls Logo

Endress+Hauser PROline promag 53 - Cable Specifications; Signal Cable; Coil Cable; Reinforced Connecting Cables

Endress+Hauser PROline promag 53
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring Promag 53 PROFIBUS DP/PA
54 Endress+Hauser
4.2.2 Cable specifications
Signal cable
3 × 0.38 mm² PVC cable with common, braided copper shield ( 7 mm) and individually
shielded cores
With Empty Pipe Detection (EPD): 4 × 0.38 mm² PVC cable with common, braided copper
shield (7 mm) and individually shielded cores
Conductor resistance: 50 km
Capacitance: core/shield: 420 pF/m
Operating temperature: –20 to +80 °C
Conductor cross-section: max. 2.5 mm²
Coil cable
2 × 0.75 mm² PVC cable with common, braided copper shield (Ø 7 mm)
Conductor resistance: 37 km
Capacitance: core/core, shield grounded: 120 pF/m
Operating temperature: –20 to +80 °C
Conductor cross-section: max. 2.5 mm²
Test current for cable insulation: 1433 V AC rms 50/60 Hz or 2026 V DC
A0003194
Fig. 32: Cable cross-section
a Signal cable
b Coil current cable
1=Core, 2=Core insulation, 3=Core shield, 4=Core jacket, 5 = Core reinforcement, 6 = Cable shield,
7=Outer jacket
Reinforced connecting cables
As an option, Endress+Hauser can also deliver reinforced connecting cables with an
additional, reinforcing metal braid.
We recommend such cables for the following cases:
Directly buried cable
Cables endangered by rodents
Device operation which should comply with the IP 68 (NEMA 6P) standard of protection
Operation in zones of severe electrical interference
The measuring device complies with the general safety requirements in accordance with
EN 61010 and the EMC requirements of IEC/EN 61326.
"
Caution!
Grounding is by means of the ground terminals provided for the purpose inside the
connection housing. Keep the stripped and twisted lengths of cable shield to the terminals
as short as possible.
1
2
3
4
5
6
7
ab

Table of Contents