Proline Promag W 400
10 Endress+Hauser
EtherNet/IP
Standards In accordance with IEEE 802.3
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output
4-20 mA
Failure mode Selectable (as per NAMUR recommendation NE 43):
Minimum value: 3.6 mA
Maximum value: 22 mA
Defined value: 3.59 to 22.5 mA
Actual value
Last valid value
0-20 mA
Failure mode Choose from:
Maximum alarm:22 mA
Defined value: 0 to 22.5 mA
HART
Device diagnostics Device condition can be read out via HART Command 48
Pulse/frequency/switch output
Pulse output
Failure mode Choose from:
Actual value
No pulses
Frequency output
Failure mode Choose from:
Actual value
Defined value: 0 to 12 500 Hz
0 Hz
Switch output
Failure mode Choose from:
Current status
Open
Closed
EtherNet/IP
Device diagnostics Device condition can be read out in Input Assembly
Local display
Plain text display With information on cause and remedial measures
Backlight Red backlighting indicates a device error.
Status signal as per NAMUR recommendation NE 107