Proline Promag W 400
16 Endress+Hauser
Supply voltage
Order code for "Power supply" Terminal numbers
1 (L+/L) 2 (L-/N)
Option L
(wide range power unit)
AC100 to 240 V
AC/DC24 V
EtherNet/IP signal transmission
Order code for "Output" Connection via
Option N EtherNet/IP connector
Remote version
E1
E2
GND
E
S1
E1
E2
S2
GND
E
S
5
7
4
37
42 41
6
5
7
8
4
37 36
n.c. n.c.
21
1
2
n.c.
42 41
A
B
A0020534
1 Remote version terminal assignment
A Transmitter wall-mount housing
B Sensor connection housing
1 Electrode cable
2 Coil current cable
n.c. Not connected, insulated cable shields
Terminal No. and cable colors: 6/5 = brown; 7/8 = white; 4 = green; 36/37 = yellow
Pin assignment, device plug
Order codes for the M12x1 plug, see the "Order code for electrical connection" column:
EtherNet/IP (→ 15)
EtherNet/IP
EtherNet/IP (on the device side)
A0016812
Pin Assignment Coding Plug/socket
1 + Tx D Socket
2 + Rx
3 - Tx
4 - Rx
Recommended plug:
• Binder, series 763, part no. 99 3729 810 04
• Phoenix, part no. 1543223 SACC-M12MSD-4Q
• When using the device in a hazardous location: Use a suitably certified plug.