Operation Proline Promag W 400 EtherNet/IP
100 Endress+Hauser
11 Operation
11.1 Read out and modify current Ethernet settings
If the Ethernet settings such as the IP address of the measuring device are unknown, they
can be read out and modified as explained in the following example for an IP address.
1
2
3
4
1
2
3
4
1
2
ON OFF
Default Ethernet network settings
IP 192.168.1.212
Write protection
128
64
32
16
8
4
2
1
IP Address
setting
(last octet)
A0023058
Prerequisite
Software addressing is enabled: All the DIP switches for hardware addressing are set to
OFF. →  46
Measuring device is switched on.
1. Set the DIP switch for "Default Ethernet network settings, IP 192.168.1.212" from
OFFON.
2. Restart the device.
The device's Ethernet settings are reset to their factory settings:
IP address: 192.168.1.212; Subnet mask: 255.255.255.0; Default gateway:
192.168.1.212
3. Enter the default setting for the IP address in the address line of the Web browser.
4. Navigate to IP address parameter in the operating menu: "Setup" menu
→ Communication → IP address
The parameter displays the configured IP address.
5. Change the IP address of the device if necessary.
6. Set the DIP switch for "Default Ethernet network settings, IP 192.168.1.212" from ON
OFF.
7. Restart the device.
The modified IP address of the device is now enabled.
11.2 Reading the device locking status
The write protection types that are currently active can be determined using the Locking
status parameter.
Navigation
"Operation" menu → Locking status