Proline Promag W 400 EtherNet/IP Operation
Endress+Hauser 103
Function scope of "Reset all totalizers" parameter
Options Description
Reset + totalize Resets all totalizers to 0 and restarts the totaling process. This deletes all the flow
values previously totalized.
Navigation
"Operation" menu → Operation
‣
Totalizer handling
Control Totalizer 1 to 3
Preset value 1 to 3
Reset all totalizers
Parameter overview with brief description
Parameter Description Selection / User entry Factory setting
Control Totalizer 1 to 3 Control totalizer value. • Totalize
• Reset + hold
• Preset + hold
• Reset + totalize
• Preset + totalize
Totalize
Preset value 1 to 3 Specify start value for totalizer. Signed floating-point number 0 l
Reset all totalizers Reset all totalizers to 0 and start. • Cancel
• Reset + totalize
Cancel
11.8 Showing data logging
In the device, the extended function of the HistoROM must be enabled (order option) so
that the Data logging submenu appears. This contains all the parameters for the
measured value history.
The data logging history is also available via the FieldCare plant asset management
tool → 68.
Function scope
• A total of 1000 measured values can be stored
• 4 logging channels
• Adjustable logging interval for data logging
• Display of the measured value trend for each logging channel in the form of a chart
A0016222
28 Chart of a measured value trend