Proline Promag W 400 EtherNet/IP Installation
Endress+Hauser 21
5 × DN
2 × DN
A0016275
To keep within the in-service maximum permissible errors for custody transfer no
additional requirements apply with regard to the graphic illustrated above.
Installation dimensions
For the dimensions and installation lengths of the device, see the "Technical
Information" document, "Mechanical construction" section
6.1.2 Requirements from environment and process
Ambient temperature range
Transmitter –40 to +60 °C (–40 to +140 °F)
Local display –20 to +60 °C (–4 to +140 °F), the readability of the display may be
impaired at temperatures outside the temperature range.
Sensor
Liner Do not exceed or fall below the permitted temperature range of the liner .
If operating outdoors:
Install the measuring device in a shady location.
Avoid direct sunlight, particularly in warm climatic regions.
Avoid direct exposure to weather conditions.
Temperature tables
Observe the interdependencies between the permitted ambient and fluid
temperatures when operating the device in hazardous areas.
For detailed information on the temperature tables, see the separate document
entitled "Safety Instructions" (XA) for the device.
System pressure
A0015594