Proline Promag W 400 EtherNet/IP System integration
Endress+Hauser 71
9.4 Cyclic data transmission
Cyclic data transmission when using the device master file (GSD).
9.4.1 Block model
The block model shows which input and output data the measuring device makes available
for implicit messaging. Cyclical data exchange is performed using an EtherNet/IP scanner,
e.g. a distributed control system etc.
Measuring device Control system
Transducer
Block
Input Assembly Fix
(Assem100) 44 Byte
→ 72
Permanently assigned
input group
→
EtherNet/IP
Ouput Assembly Fix
(Assem102) 64 Byte
→ 73
Permanently assigned
output group
←
Input Assembly Fix
(Assem101) 88 Byte
→ 73
Configurable
input group
→
9.4.2 Input and output groups
Possible configurations
Configuration 1: Exclusive Owner Multicast
Input Assembly Fix Instance Size [byte] min. RPI (ms)
Input Assembly Configurable Configuration 0 x 64 398 –
Output Assembly Fix O → T Configuration 0 x 66 64 5
Input Assembly Fix T → O Configuration 0 x 64 44 5
Configuration 2: Input Only Multicast
Input Assembly Fix Instance Size [byte] min. RPI (ms)
Input Assembly Configurable Configuration 0 x 68 398 –
Output Assembly Fix O → T Configuration 0 x C7 – –
Input Assembly Fix T → O Configuration 0 x 64 44 5
Configuration 3: Exclusive Owner Multicast
Input Assembly Configurable Instance Size [byte] min. RPI (ms)
Input Assembly Configurable Configuration 0 x 68 398 –
Output Assembly Fix O → T Configuration 0 x 66 64 5
Input Assembly Fix T → O Configuration 0 x 65 88 5
Configuration 4: Input Only Multicast
Input Assembly Configurable Instance Size [byte] min. RPI (ms)
Input Assembly Configurable Configuration 0 x 68 398 –
Output Assembly Fix O → T Configuration 0 x C7 – –
Input Assembly Fix T → O Configuration 0 x 64 88 5