Proline Promag W 800
12 Endress+Hauser
Terminal assignment Transmitter
A0017259
Transmitter terminal assignment
A Terminals: connection of external power supply (optional)
B Terminals: signal transmission via inputs and outputs, connection of remote version
Terminals (A): connection of external power supply (optional)
Terminals (B): signal transmission via inputs and outputs, connection of remote version
Power supply Power from batteries
• 3.6 V DC
• 19 Ah nominal capacity at 20 °C (per battery)
• Max. power: 200 mW
Battery life ä 11
Supply voltage via external power supply (optional)
• 100 to 240 V AC / 12 to 60 V DC
• 44 to 66 Hz
• Max. power: 3 W
• A battery to act as a back up if the power supply fails
"
Caution!
The values specified for the supply voltage may not be exceeded.
Power consumption Switch-on current:
• Max. 30 A at 240 V AC
• Max. 6 A at 24 V DC
17
16 15 14
10
98765
13
12 11
4321
)
12
3
A
B
External power supply
Terminal Connection
1 Protective ground
2N –
3L +
Inputs Outputs
Terminal Connection Terminal Connection
5 Input 1 (+) 14 Shield, output 1 and 2
6 Input 1 (–) 15 Output 1 (+)
16 Output 2 (+)
17 Output 1 and 2 (–)
Remote version connection
Terminal Connection
1 Electrode E1 (brown)
2Electrode E2 (white)
3 Shield, electrode E1 (brown)
4 Shield, electrode E2 (white)
11 Reference electrode (green)
12 Coil current cable B2 (black)
13 Coil current cable B1 (black)