Operation Proline Promag W 800
74 Endress+Hauser
Parameter overview with brief description
Parameter Description User entry / User interface
Activate SW option Enter the application package code or code of another re-
ordered functionality to enable it.
Positive integer
Software option overview Shows all enabled software options. Extended data logger
Extended HistoROM
Heartbeat Verification
Custody transfer
Heartbeat Monitoring
11.6 Updating the firmware
Firmware updates are available in the Download Area of the Endress+Hauser website:
www.endress.com → Downloads
Specify the following details for the "Device driver":
Type: "Firmware Flash File"
Product root: "5W8C"
Process communication: "Modbus RS485"
Device type: "0x6463 (Promag 800)"
Select device version
Start the search
1. Extract the ZIP file.
2. Save the extracted "Firmware Flash File" to the mobile device.
iOS: Files → SmartBlue → UpdatePackages
Android: Internal memory → SmartBlue → Firmware
3. Connect to the measuring device via the SmartBlue app.
4. In the SmartBlue app, open: System → Software configuration → Firmware update.
5. Wait until the firmware is loaded.
6. Start the firmware update and let it run through to the end.
7. Wait until the measuring device is restarted.
The new firmware has been successfully installed.
11.7 Checking, verifying or calibrating the measuring
device
The measuring device is set as follows when checked, verified or calibrated.
For devices with a power supply unit which are operated with an external power
supply, the measuring interval is automatically switched to the minimum value.
1. Connect to the measuring device via the SmartBlue app.
2. In the SmartBlue app: Application → Sensor → Sensor adjustment → Open
measurement interval value.
3. Set the value to 0.25 s.
This minimizes the measurement times required on the calibration rig.
4. Once the measurements are complete, the measuring interval must be reset to 15 s
(factory setting) to preserve the battery life.