Technical data Proline Promag W 800
96 Endress+Hauser
16 Technical data
16.1 Application
The measuring device is intended only for the flow measurement of liquids with a
minimum conductivity of 20 µS/cm.
To ensure that the device remains in proper operating condition for its service life, use the
measuring device only for media against which the process-wetted materials are
sufficiently resistant.
16.2 Function and system design
Measuring principle Electromagnetic flow measurement on the basis of Faraday's law of magnetic induction.
Measuring system The device consists of a transmitter and a sensor.
Proline Promag 800 - Standard
Compact version – transmitter and sensor form a mechanical unit.
Proline Promag 800 - Advanced
Two device versions are available:
• Compact version – transmitter and sensor form a mechanical unit.
• Remote version - transmitter and sensor are mounted in separate locations.
For information on the structure of the measuring device → 13
16.3 Input
Measured variable Direct measured variables
• Volume flow (proportional to induced voltage)
• Electrical conductivity
• Pressure (optional)
Measuring range Typically v = 0.01 to 10 m/s (0.03 to 33 ft/s) with the specified accuracy
Electrical conductivity: ≥ 20 μS/cm for liquids in general
Flow characteristic values in SI units
Nominal
diameter
Recommended
Flow rate
Factory settings
min./max. full scale value
(v ~ 0.3/10 m/s)
Pulse value
(~ 2 pulse/s)
Low flow cut off
(v ~ 0.04 m/s)
[mm] [in] [m
3
/h] [m
3
] [m
3
/h]
25 1 9 to 300 dm
3
/min 0.5 dm
3
1 dm
3
/min
32 – 15 to 500 dm
3
/min 1 dm
3
2 dm
3
/min
40 1 ½ 25 to 700 dm
3
/min 1.5 dm
3
3 dm
3
/min
50 2 35 to 1 100 dm
3
/min 2.5 dm
3
5 dm
3
/min
65 – 60 to 2 000 dm
3
/min 5 dm
3
8 dm
3
/min
80 3 90 to 3 000 dm
3
/min 5 dm
3
12 dm
3
/min
100 4 145 to 4 700 dm
3
/min 10 dm
3
20 dm
3
/min