Device Functions Proline Promass 80 7 Group TOTALIZER 1/2
Endress+Hauser 21
UNIT
TOTALIZER
Use this function to define the unit for the totalizer measured variable, as selected
beforehand.
Options (for the MASS FLOW assignment):
Metric
→ g; kg; t
US
→ oz; lb; ton
Factory setting:
Depends on nominal diameter and country, [value] / [g ...kg or US oz...US ton]
corresponding to the totalizer unit factory setting (see Page 63 ff.)
Options (for the VOLUME FLOW assignment):
Metric
→ cm
3
; dm
3
; m
3
; ml; l; hl; Ml
US
→ cc; af; ft
3
; oz f; gal; Kgal; Mgal; bbl (normal fluids); bbl (beer); bbl
(petrochemicals); bbl (filling tanks)
Imperial
→ gal; Mgal; bbl (beer); bbl (petrochemicals)
Options (for the CORRECTED VOLUME FLOW assignment):
Metric
→ Nl; Nm
3
US → Sm
3
; Scf
Factory setting:
Depends on nominal diameter and country, [value] / [dm
3
...m
3
or US gal...US Mgal]
corresponding to the totalizer unit factory setting (see Page 63 ff.)
TOTALIZER MODE Use this function to define how the flow components are to be totalized.
Options:
BALANCE
Positive and negative flow components. The positive and negative flow components are
balanced. In other words, net flow in the flow direction is registered.
FORWARD
Only positive flow components are totalized.
REVERSE
Only negative flow components are totalized.
Factory setting:
Totalizer 1 = BALANCE
Totalizer 2 = FORWARD
RESET TOTALIZERS Use this function to reset the sum and the overflow of the totalizer to “zero” (= RESET).
Options:
NO
YES
Factory setting:
NO
! Note!
If the device has a status input and is appropriately configured, a reset for the totalizer can
also be triggered by a pulse.
Function description TOTALIZER 1/2