9 Group CURRENT OUTPUT 1/2 Device Functions Proline Promass 80
24 Endress+Hauser
CURRENT SPAN
(contd)
Current span, operational range and signal on alarm level
A0001222
A = Current span
1 = Operational range (measuring information)
2 = Lower signal on alarm level
3 = Upper signal on alarm level
! Note!
• If the measured value exceeds the measuring range (as defined in the functions VALUE
0_4 mA and VALUE 20 mA a notice message is generated (#351...352, current span).
• In case of a fault the behavior of the current output is according to the selected option
in the function FAILSAFE MODE. Change the error category in the function ASSIGN
SYSTEM ERROR to generate a fault message instead of a notice message.
VALUE 0_4 mA
! Note!
This function is not available unless the DENSITY, REFERENCE DENSITY or
TEMPERATURE option was selected in the ASSIGN CURRENT OUTPUT function.
Use this function to assign a value to the 0/4 mA current, (see “Setting the span by
means of the 0_4 mA and 20 mA value“ on Page 25).
User input:
5-digit floating-point number (with sign for the TEMPERATURE measured variable)
Factory setting:
0.5 [kg/l] or –50 [°C]
VALUE 20 mA Use this function to assign a value to the 20 mA current, (see “Setting the span by means
of the 0_4 mA and 20 mA value” on Page 25).
User input:
5-digit floating-point number (with sign for the MASS FLOW, VOLUME FLOW,
CORRECTED VOLUME FLOW and TEMPERATURE measured variables)
Factory setting:
Depends on nominal diameter [kg/h] or 2 [kg/l] or 200 [°C]
Function description CURRENT OUTPUT 1/2
123
I[mA]
a123
0-20 mA
4-20 mA
4-20 mA NAMUR
4-20 mA US
0-20 mA (25 mA)
4-20 mA (25 mA)
0 - 20.5 mA 0 22
4 - 20.5 mA
222
3.8 - 20.5 mA
3.5 22.6
3.9 - 20.8 mA
3.75 22.6
0-24mA 0 25
4-24mA 2 25
4-20 mA HART 4 - 20.5 mA
222
4-20 mA HART NAMUR
3.8 - 20.5 mA
3.5 22.6
4-20 mA HART US
3.9 - 20.8 mA
3.75 22.6
4-20 mA (25 mA) HART
4-24mA 2 25