Proline Promass E 100
Endress+Hauser 19
Cycle times From 8 ms
Polarity Auto-polarity for automatic correction of crossed TxD and RxD pairs
Supported connections • 1 x AR (Application Relation)
• 1 x Input CR (Communication Relation)
• 1 x Output CR (Communication Relation)
•
1 x Alarm CR (Communication Relation)
Configuration options for
measuring device
• DIP switches on the electronics module, for device name assignment (last
part)
• Manufacturer-specific software (FieldCare, DeviceCare)
• Web browser
• Device master file (GSD), can be read out via the integrated Web server of
the measuring device
Configuration of the device
name
• DIP switches on the electronics module, for device name assignment (last
part)
• DCP protocol
Output values
(from measuring device to
automation system)
Analog Input module (slot 1 to 14)
• Mass flow
• Volume flow
• Corrected volume flow
• Target mass flow
• Carrier mass flow
• Density
• Reference density
• Concentration
• Temperature
• Carrier pipe temperature
• Electronic temperature
• Oscillation frequency
• Oscillation amplitude
• Frequency fluctuation
• Oscillation damping
• Tube damping fluctuation
• Signal asymmetry
• Exciter current
Discrete Input module (slot 1 to 14)
• Empty pipe detection
• Low flow cut off
Diagnostics Input module (slot 1 to 14)
• Last diagnostics
• Current diagnosis
Totalizer 1 to 3 (slot 15 to 17)
• Mass flow
• Volume flow
• Corrected volume flow
Heartbeat Verification module (fixed assignment)
Verification status (slot 23)
The range of options increases if the measuring device has one or more
application packages.