Proline Promass E 100
36 Endress+Hauser
PROFIBUS DP
A0028765
13 Connection example for PROFIBUS DP, non-hazardous area and Zone 2/Div. 2
1
Control system (e.g. PLC)
2 Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications
3 Transmitter
If baud rates > 1.5 MBaud an EMC cable entry must be used and the cable shield must continue
as far as the terminal wherever possible.
Modbus RS485
Modbus RS485, non-hazardous area and Zone 2/Div. 2
A0028765
14 Connection example for Modbus RS485, non-hazardous area and Zone 2/Div. 2
1
Control system (e.g. PLC)
2 Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications → 39
3 Distribution box
4
Transmitter