Proline Promass E 100
Endress+Hauser 79
Reliable operation
Operation in the following languages:
Via "FieldCare", "DeviceCare" operating tool:
English, German, French, Spanish, Italian, Chinese, Japanese
Via integrated Web browser(only available for device versions with HART, PROFIBUS DP,
PROFINET and EtherNet/IP):
English, German, French, Spanish, Italian, Dutch, Portuguese, Polish, Russian, Turkish, Chinese,
Japanese, Bahasa (Indonesian), Vietnamese, Czech, Swedish, Korean
Uniform operating philosophy applied to operating tools and Web browser
If replacing the electronic module, transfer the device configuration via the plug-in memory
(HistoROM DAT) which contains the process and measuring device data and the event logbook. No
need to reconfigure.
For devices with Modbus RS485, the data recovery function is implemented without the plug-in
memory (HistoROM DAT).
Efficient diagnostics increase measurement availability
Troubleshooting measures can be called up via the operating tools and web browser
Diverse simulation options
Status indicated by several light emitting diodes (LEDs) on the electronic module in the housing
compartment
Local display
A local display is only available for device versions with the following communication protocols:
HART, PROFIBUS-DP, PROFINET
, EtherNet/IP
The local display is only available with the following device order code:
Order code for "Display; operation", option B: 4-line; illuminated, via communication
Display element
4-line liquid crystal display with 16 characters per line.
White background lighting; switches to red in event of device errors.
Format for displaying measured variables and status variables can be individually configured.
Permitted ambient temperature for the display: –20 to +60 °C (–4 to +140 °F). The readability of
the display may be impaired at temperatures outside the temperature range.
Remote operation Via HART protocol
This communication interface is available in device versions with a HART output.
1 2 3 5
7
4 6
A0016948
37
Options for remote operation via HART protocol
1
Control system (e.g. PLC)
2 Field Communicator 475
3 Computer with operating tool (e.g. FieldCare, AMS Device Manager, SIMATIC PDM)
4 Commubox FXA195 (USB)
5 Field Xpert SFX350 or SFX370
6 VIATOR Bluetooth modem with connecting cable
7 Transmitter
Via PROFIBUS DP network
This communication interface is available in device versions with PROFIBUS DP.