Endress+Hauser Proline Promass E TB2 HART - 18.4 Output

Endress+Hauser Proline Promass E TB2 HART
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data Proline Promass E TB2 HART
98 Endress+Hauser
g
max(F)
Maximum full scale value for liquid [kg/h]
g
max(G)
< g
max(F)
g
max(G)
can never be greater than g
max(F)
r
G
Gas density in [kg/m
3
] at operating conditions
DN x
[mm] [in] [kg/m
3
]
8 3/8 85
15 ½ 110
25 1 125
40 1 ½ 125
50 2 125
To calculate the measuring range, use the Applicator sizing tool (® ä 94)
Calculation example for gas
Sensor: Promass E, DN 50
Gas: Air with a density of 60.3 kg/m
:
(at 20 °C and 50 bar)
Measuring range (liquid): 70 000 kg/h
x = 125 kg/m
3
(for Promass E DN 50)
Maximum possible full scale value:
g
max(G)
= g
max(F)
× r
G
: x = 70 000 kg/h × 60.3 kg/m
3
: 125 kg/m
:
= 33 800 kg/h
Recommended measuring range
"Flow limit" section (® ä 103)
Operable flow range Greater than 1000: 1. Flow rates above the preset full scale value do not overload the amplifier so
the totalized values are registered correctly.
18.4 Output
Output signal
2-wire:
Current output 1: 4-20 mA HART
Current output 2: 4-20 mA
Lower-range value, full scale value and time constant (0.07 to 999 s) can be set
Signal on alarm Maintenance information can be viewed via the following interfaces:
Local display:
Error symbol (in accordance with NAMUR Recommendation NE 107)
Plain text display
Current output: failsafe mode selectable (in accordance with NAMUR Recommendation NE 43):
Minimum alarm: 3.6 mA
Maximum alarm (= factory setting): 22 mA
Digital interface such as HART communication or CDI service interface (in accordance with
NAMUR Recommendation NE 107)
Galvanic isolation All circuits for the outputs are galvanically isolated from each other.