Proline Promass E TB2 HART Technical data
Endress+Hauser 99
Protocol-specific data
For information on the device description files (® ä 49)
For information on the HART device variables and measured values
For information on the HART commands
18.5 Power supply
Terminal assignment
Order version
Output
Terminal numbers
3 (+) 4 (-) 1 (+) 2 (-)
8E2B**-**C******** 4-20 mA 4-20 mA HART
Supply voltage
Order version,
output
U
S
*
(supply voltage)
I
max
(output current)
8E2B**-**C******** 18 to 30 V DC 22.0 mA
*
Supply voltage range without load. For information on the supply voltage with a load (® ä 27)
Power consumption Operation with current output 1: 65 to 660 mW
Operation with current output 1 and 2: 130 to 1 320 mW
Power supply failure Totalizers stop at the last value measured.
Configuration is retained in the HistoROM.
Error messages (incl. total operated hours) are stored.
Electrical connection
(® ä 25)
Load
(® ä 27)
Potential equalization No special measures for potential equalization are required.
Terminals Plug-in spring terminals for wire cross-sections 0.5 to 2.5 mm
2
(20 to 14 AWG)
Cable entries
Cable gland: M20 × 1.5 with cable Æ 6 to 12 mm (0.24 to 0.47 in)
Thread for cable entry: ½" NPT, G ½"
Cable specification
Permitted temperature range: –40 °C (–40 °F) to³ 80 °C (176 °F); at least ambient temperature
+ 20 K
A normal device cable suffices if only the analog signal is used.
A shielded cable is recommended if using the HART protocol. Observe grounding concept of the
plant.