Commissioning Proline Promass F 100 Modbus RS485
66
Parameter overview with brief description
Parameter Prerequisite Description Selection Factory setting
Assign process variable Select process variable for
totalizer.
Off
Mass flow
Volume flow
Corrected volume
flow
Target mass flow
*
Carrier mass flow
*
Mass flow
Unit totalizer One of the following options is
selected in the Assign process
variable parameter (→  66)
of the Totalizer 1 to n
submenu:
Volume flow
Mass flow
Corrected volume flow
Target mass flow
*
Carrier mass flow
*
Select process variable totalizer
unit.
Unit choose list Country-specific:
kg
lb
Totalizer operation mode One of the following options is
selected in the Assign process
variable parameter (→  66)
of the Totalizer 1 to n
submenu:
Volume flow
Mass flow
Corrected volume flow
Target mass flow
*
Carrier mass flow
*
Select totalizer calculation
mode.
Net flow total
Forward flow total
Reverse flow total
Net flow total
Failure mode One of the following options is
selected in the Assign process
variable parameter (→  66)
of the Totalizer 1 to n
submenu:
Volume flow
Mass flow
Corrected volume flow
Target mass flow
*
Carrier mass flow
*
Define totalizer behavior in
alarm condition.
Stop
Actual value
Last valid value
Stop
* Visibility depends on order options or device settings
10.5.5 Using parameters for device administration
The Administration submenu systematically guides the user through all the parameters
that can be used for device administration purposes.
Navigation
"Setup" menu → Advanced setup → Administration
Administration
Device reset
→  67