Diagnostics and troubleshooting Proline Promass F 100 Modbus RS485
80
Parameter overview with brief description
Parameters Description Selection Factory setting
Failure mode Select measured value
output behavior when a
diagnostic message occurs
via Modbus
communication.
This effect of this
parameter depends
on the option
selected in the
Assign diagnostic
behavior
parameter.
• NaN value
• Last valid value
NaN º not a number
NaN value
12.5 Adapting the diagnostic information
12.5.1 Adapting the diagnostic behavior
Each item of diagnostic information is assigned a specific diagnostic behavior at the
factory. The user can change this assignment for specific diagnostic information in the
Diagnostic behavior submenu.
Expert → System → Diagnostic handling → Diagnostic behavior
You can assign the following options to the diagnostic number as the diagnostic behavior:
Options Description
Alarm The device stops measurement. The measured value output via Modbus RS485 and the
totalizers assume the defined alarm condition. A diagnostic message is generated.
Warning The device continues to measure. The measured value output via Modbus RS485 and the
totalizers are not affected. A diagnostic message is generated.
Logbook entry only The device continues to measure. The diagnostic message is entered only in the Event
logbook submenu.
Off The diagnostic event is ignored, and no diagnostic message is generated or entered.
12.6 Overview of diagnostic information
The amount of diagnostic information and the number of measured variables affected
increase if the measuring device has one or more application packages.
In the case of some items of diagnostic information, the diagnostic behavior can be
changed. Change the diagnostic information → 80
Diagnostic
number
Short text Remedy instructions Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
Diagnostic of sensor
022 Sensor temperature 1. Change main electronic
module
2. Change sensor
F Alarm