Proline Promass F 100 Modbus RS485 Technical data
97
Current output 4 to 20 mA
4 to 20 mA
Failure mode Choose from:
4 to 20 mA in accordance with NAMUR recommendation NE 43
4 to 20 mA in accordance with US
Min. value: 3.59 mA
Max. value: 22.5 mA
Freely definable value between: 3.59 to 22.5 mA
Actual value
Last valid value
Pulse/frequency/switch output
Pulse output
Failure mode Choose from:
Actual value
No pulses
Frequency output
Failure mode Choose from:
Actual value
0 Hz
Defined value: 0 to 12 500 Hz
Switch output
Failure mode Choose from:
Current status
Open
Closed
Modbus RS485
Failure mode Choose from:
NaN value instead of current value
Last valid value
Interface/protocol
Via digital communication:
Modbus RS485
Via service interface
CDI-RJ45 service interface
Plain text display With information on cause and remedial measures
Light emitting diodes (LED)
Status information Status indicated by various light emitting diodes
The following information is displayed depending on the device version:
Supply voltage active
Data transmission active
Device alarm/error has occurred
Diagnostic information via light emitting diodes