Proline Promass I 100
42 Endress+Hauser
Mounting Safety Barrier
Promass 100
> 22.5
(> 0.89)
> 22.5
(> 0.89)
A0016894
19 Minimum distance between additional Safety Barrier Promass 100 or other modules.Engineering unit mm
(in)
Environment
Ambient temperature range
Measuring device Non-Ex –40 to +60 °C (–40 to +140 °F)
Ex na, NI version –40 to +60 °C (–40 to +140 °F)
Ex ia, IS version • –40 to +60 °C (–40 to +140 °F)
• –50 to +60 °C (–58 to +140 °F) (Order code for "Test, certificate",
option JM
Local display –20 to +60 °C (–4 to +140 °F)
The readability of the display may be impaired at temperatures outside
the temperature range.
Safety Barrier Promass 100 –40 to +60 °C (–40 to +140 °F)
‣
If operating outdoors:
Avoid direct sunlight, particularly in warm climatic regions.
Weather protection covers can be ordered from Endress+Hauser: see "Accessories" section
Temperature tables
In the following tables, the following interdependencies between the maximum medium
temperature for T1-T6 and the maximum ambient temperature T
a
apply when operating the device
in hazardous areas.
Ex ia,
C
CSA
US
IS
SI units
Order code for "Housing" T
a
[°C]
T6
[85 °C]
T5
[100 °C]
T4
[135 °C]
T3
[200 °C]
T2
[300 °C]
T1
[450 °C]
Option A "Compact coated alu"
Option B "Compact hygienic,
stainless"
35 50 85 120 150
1)
150
2)
150
2)
50 – 85 120 150
1)
150
2)
150
2)
60 – – 120 150
1)
150
2)
150
2)
Option C "Ultra compact hygienic,
stainless, M12 device plug"
35 50 85 120 150
1)
150
2)
150
2)