Proline Promass I 100 Modbus RS485 Commissioning
Endress+Hauser 49
10.3.4 Configuring the low flow cut off
The Low flow cut off submenu contains parameters that have to be set for configuring the
low flow cut off.
Navigation path
"Setup" menu Low flow cut off
Structure of the submenu
Low flow cut off
Assign process variable
On value low flow cut off
Off value low flow cutoff
Pressure shock suppression
Parameter overview with brief description
Parameter Prerequisite Description Selection/
User entry
Factory
setting
Assign process
variable
– Select the process
variable for low flow cut
off.
• Off
• Mass flow
• Volume flow
• Corrected
volume flow
Mass flow
On value low
flow cut off
One of the following options
is selected in the Assign
process variable parameter:
• Mass flow
• Volume flow
• Corrected volume flow
Enter the on value for
low flow cut off.
Max. 15-digit,
positive floating-
point number
For liquids:
depends on
country and
nominal
diameter
Off value low
flow cut off
One of the following options
is selected in the Assign
process variable parameter:
• Mass flow
• Volume flow
• Corrected volume flow
Enter the off value for
low flow cut off.
0 to 100 % 50 %
Pressure shock
suppression
One of the following options
is selected in the Assign
process variable parameter:
• Mass flow
• Volume flow
• Corrected volume flow
Enter the time interval
for signal suppression (=
active pressure shock
suppression).
0 to 100 s 0 s