Technical data Proline Promass I 100 Modbus RS485
80 Endress+Hauser
16.5 Power supply
Terminal assignment ( 26)
Pin assignment, device plug ( 28)
Supply voltage Transmitter
• For device version with all communication types except Modbus RS485 intrinsically safe:
DC20 to 30 V
• For device version with Modbus RS485100 intrinsically safe: power supply via Safety
Barrier Promass 100
The power unit must be tested to ensure it meets safety requirements (e.g. PELV, SELV).
Safety Barrier Promass 100
DC20 to 30 V
Power consumption Transmitter
Order code for
"Output"
Maximum
Power consumption
Option M: Modbus RS485, for use in non-hazardous areas and
Zone 2/Div. 2
3.5 W
Option M: Modbus RS485, for use in intrinsically safe areas 2.45 W
Safety Barrier Promass 100
Order code for
"Output"
Maximum
Power consumption
Option M: Modbus RS485, for use in intrinsically safe areas 4.8 W
Current consumption Transmitter
Order code for
"Output"
Maximum
Current consumption
Maximum
switch-on current
Option M: Modbus RS485, for use in non-hazardous areas and
Zone 2/Div. 2
90 mA 10 A (< 0.8 ms)
Option M: Modbus RS485, for use in intrinsically safe areas 145 mA 16 A (< 0.4 ms)
Safety Barrier Promass 100
Order code for
"Output"
Maximum
Current consumption
Maximum
switch-on current
Option M: Modbus RS485, for use in intrinsically safe areas 230 mA 10 A (< 0.8 ms)
Power supply failure • Totalizers stop at the last value measured.
• Depending on the device version, the configuration is retained in the device memory or
in the plug-in memory (HistoROM DAT).
• Error messages (incl. total operated hours) are stored.
Electrical connection ( 29)