Proline Prowirl 72 FOUNDATION Fieldbus 11 Operation via FOUNDATION Fieldbus
Endress + Hauser 107
11. 7 Endress+Hauser parameters:
Transducer Block "Display"
The following table shows all the Endress+Hauser-specific parameters of the Transducer Block
"Display". These can only be changed after entering an enabling code in the "Un-/Locking - Access
Code" parameter.
Transducer Block "Display" (Endress+Hauser parameters) / base index 700
Parameter Write access for
operating mode
(MODE_BLK)
Description
! Note!
The FOUNDATION Fieldbus parameters of this block are described on Page 87.
Un-/Locking -
Access Code
AUTO - OOS All data of the measuring system are protected against inadvertent change.
Programming of the manufacturer-specific parameters is disabled and the
settings cannot be changed until a code is entered in this function.
You can enable programming by entering the:
• Code 72 (factory setting)
• Personal code, see "Un-/Locking – Define Private Code" parameter
(Page 108) Transducer Block "Display"
User input:
Max. 4-digit number (0 to 9999)
! Note!
• If write protection is enabled, access to manufacturer-specific parameters
is denied even if the right code is entered. Write protection can be
enabled or disabled by means of DIP switches (Page 35).
• You can disable programming again by entering any number in this
function (other than the Access Code).
• The Endress+Hauser service organization can be of assistance if you
mislay your private code.
• Certain parameters can only be altered if a special Service Code is
entered. This Service Code is known to your Endress+Hauser service
organization. Please contact your Endress+Hauser service point if
anything needs clarification.
Un-/Locking -
Access Status
Read only Use this function to display the current status of the possibilities for accessing
the manufacturer-specific parameters of the device.
Display:
• LOCKED (parameters cannot be modified)
• ACCESS CUSTOMER (parameters can be modified)
• ACCESS SERVICE (parameters can be modified, access to service level)