3.4 Post-installation check
Perform the following checks after installing the measuring device in the piping:
Device condition and specifications Notes
Is the device damaged (visual inspection)?
Do the process temperature/pressure, ambient temperature, measuring range
etc. correspond to the specifications of the device?
see Page 62 ff.
Installation Notes
Does the arrow on the pipe stand or on the sensor match the direction of flow
through the pipe?
Are the measuring point number and labeling correct (visual inspection)? –
Is the orientation chosen for the sensor correct, in other words suitable for
sensor type, fluid properties (outgassing, with entrained solids) and fluid
temperature?
see Page 11 ff.
Process environment / process conditions Notes
Is the measuring device protected against moisture and direct sunlight?