11 Operation via FOUNDATION Fieldbus Proline Prowirl 72 FOUNDATION Fieldbus
88 Endress + Hauser
BLOCK_ERR Read only The active block errors appear on the display.
Display:
OUT OF SERVICE
The block is in the "out of service" operating mode.
Block errors which are only shown in the Transducer Block "Diagnosis"
SIMULATE ACTIVE
Simulation via the "Simulation - Measurand"
parameter (Page 101) in the Transducer Block "Flow" is active.
MAINTENANCE NEEDED
The device must be checked since an active device error is pending.
A detailed display of the cause of the error can be called up in the
Transducer Block "Diagnosis" by means of the "Diagnosis - Actual
System Condition" parameter (Page 112).
UPDATE_
EVT
AUTO - OOS Indicates whether static block data have been altered, including date and
time.
BLOCK_ALM AUTO - OOS The current block status appears on the display with information on
pending configuration, hardware or system errors, including information
on the alarm period (date, time) when the error occurred.
! Note!
In addition, the active block alarm can be acknowledged in this
parameter group.
Prowirl 72 FF does not use this parameter to display a process alarm
since this is generated in the BLOCK_ALM parameter of the Analog
Input Function Block.
Transducer Type Read only The Transducer Block type appears on the display.
Display:
Standard flow with calibration
Transducer Error Read only The active device error appears on the display.
Possible display:
No Error (normal status)
Electronics Failure
Data Integrity Error
Mechanical Error
Configuration Error
General Error
! Note!
The display of the device error is standardized. Precise information on
the error pending is available by means of the manufacturer-specific
error display which can be read off via the Transducer Block
"Diagnosis" in the "Diagnosis - Actual System Condition" parameter.
An exact error description as well as information on rectifying errors
can be found on Page 49 ff..
FOUNDATION Fieldbus parameters (Transducer Blocks)
Parameter Write access for
operating mode
(MODE_BLK)
Description